GLOSSARY ENTRY (DERIVED FROM QUESTION BELOW) | ||||||
---|---|---|---|---|---|---|
|
10:01 Oct 10, 2019 |
Spanish to English translations [PRO] Tech/Engineering - Electronics / Elect Eng | |||||||
---|---|---|---|---|---|---|---|
|
| ||||||
| Selected response from: Thomas Walker United States Local time: 05:46 | ||||||
Grading comment
|
Summary of answers provided | ||||
---|---|---|---|---|
4 | overcurrent release |
| ||
4 | trip coil |
| ||
3 | shunt trip breaker |
|
Summary of reference entries provided | |||
---|---|---|---|
Further information |
|
overcurrent release Explanation: Sí que lo es. https://www.schneider-electric.us/en/search/19065 https://www.se.com/es/es/product/19065/bobina-de-emisión-mx-... |
| |
Login to enter a peer comment (or grade) |
shunt trip breaker Explanation: This is also referred to as a shunt trip device. It is basically a regular circuit breaker with an additional coil that can trip the breaker when an external signal is sent to the coil. One use for this device is in elevators, which typically have a shunt trip device linked to a fire alarm, which can turn the elevator off in case of fire. See this reference: https://www.reference.com/home-garden/shunt-trip-breakers-wo... |
| |
Grading comment
| ||
Login to enter a peer comment (or grade) |
trip coil Explanation: I hope this helps. |
| |
Login to enter a peer comment (or grade) |
5 hrs |
Reference: Further information Reference information: From a downloaded French/English document MX : déclencheur à émission de courant MX: shunt release Bobina de emisión MX 230V con contacto auxiliar OF, compatible con los magnetotérmicos de las serie CKYB1-63 de la marca MOCUEL y con la serie C60 de las demás marcas. https://webmatel.com/MC-CKYB1-MX MX shunt release The MX release opens the circuit breaker via an impulse-type (u 20 ms) or maintained order. Opening conditions When the MX release is supplied, it automatically opens the circuit breaker. Opening is ensured for a voltage U u 0.7 x Un. https://www.se.com/au/en/faqs/FA296261/ A shunt trip device is an optional accessory in a circuit breaker that mechanically trips the breaker when power is applied to the shunt trip terminals. The power for the shunt trip does not come from within the breaker, so it must be supplied from an external source. Some circuit breakers allow field installlation of a shunt trip kit, however others require factory installation when the breaker is ordered. Check the specific breaker type for available ac and dc shunt trip voltage ratings and for the method of installation. https://www.se.com/au/en/faqs/FA87281/ -------------------------------------------------- Note added at 5 hrs (2019-10-10 15:26:16 GMT) -------------------------------------------------- Bobina de emisión Shunt trip https://www.tragamovil.es/los-raees/nuevos-raees/ -------------------------------------------------- Note added at 5 hrs (2019-10-10 15:27:19 GMT) -------------------------------------------------- • Relé diferencial + interruptor: El relé incluye el transformador de medida y el relé de detección, con un contacto de salida de baja potencia. Este contacto está pensado para actuar sobre un interruptor automático convencional, ya sea a través de la bobina de mínima o de la bobina de emisión de tensión (shunt trip). http://relesdiferencialesjuang.blogspot.com/2018/09/tipos-de... |
| ||
Note to reference poster
| |||
Login to enter a peer comment (or grade) |
Login or register (free and only takes a few minutes) to participate in this question.
You will also have access to many other tools and opportunities designed for those who have language-related jobs (or are passionate about them). Participation is free and the site has a strict confidentiality policy.